Delta-Star Air-Cooled Heat Pump
Sizing

Properly sizing your Delta Star Heat Pump

A number of factors influence the correct size of heat pump required for your application. While standard Btu calculations can be applied, and our Heat Pump Specifications can offer some guidelines, the parameters of your application will be the deciding factor in correct size selection.

Contact us today for help with sizing the perfect unit for your needs.

Things to consider:

Home Aquariums: The life support equipment on your aquarium contributes excess heat to your
system, including pumps, filters, and lighting. Tank material, surface area, plumbing, and sumps
also play a role, as do a number of other seemingly small details. Give us a call and our
experienced technicians will ask the right questions about your set-up to get the answers we need
to size the right unit for you.

Aquaculture/Hatcheries: Beyond the LSS equipment, these systems can be vast and varied in their
set-up, from small indoor hatcheries to huge outdoor fish farms. With so many specific factors to
consider, we are here to help size the right heating and chilling equipment. We have heat pumps,
chillers, heat exchangers, and boilers of every size, so give us a call and tell us what you want to
achieve and we’ll get you exactly what you need.

Hydroponics: Typically hydroponics applications have a relatively low water volume spread out over
a large area, which means a tremendous amount of heat may be gained or lost. Grow lights and
sunlight contribute significantly to water heat and encourage growth fungal growth and disease
that can be harmful to plants. Our heat pumps or chiller can help maintain the optimal growing
water temperature so you can maximize your yield. Call us for assistance with proper sizing.

Delta-Star Air-Cooled Heat Pump

MODEL
NO.

HP

NOMINAL
BTUH

R134A
REFRIGERANT
CHARGE
(OZ)

VOLTS /
PHASE

AMPS.

WATTS

WATER
FLOW
RATE
(GPM)

AIR
OUTLET
(CFM)

L

W

H

WO

WC
WATER
IN / OUT
(FPT)

DSHP-4

1/3

4,000

8.5

115

7.2

828

10-20

260

22 1/2″

13 5/8″

14″

7 1/4″

3/4″

DSHP-5

1/2

6,000

10

115

9.5

1092

12-25

350

24″

15 3/8″

15 1/2″

9 1/4″

1 1/2″

DSHP-6

1/2

6,000

10

230 / 1

4.8

1104

12-25

350

24″

15 3/8″

15 1/2″

9 1/4″

1 1/2″

DSHP-7

3/4

9500

R134A / 38

115

15.4

70

19.2

590

23 3/4″

23 3/4″

14 7/8″

9 1/4″

1 1/2″

DSHP-8

3/4

9500

R134A / 48

230 / 1

7

1610

15 – 30

590

23 3/4″

23 3/4″

14 7/8″

9 1/4″

1 1/2″

DSHP-9

1

12,000

R134A / 56

230 / 1

7.2

1656

20 – 35

610

26 1/4″

27 1/2″

17 5/8″

9 1/4″

1 1/2″

DSHP-10

1 1/2

21,000

R404A / 72

230 / 1

10.5

2415

25 – 40

772

26 1/4″

26 1/4″

17 5/8″

12″

1 1/2″

Specifications
  • 1/3 Hp – 1 ½ Hp
  • Heat or Chill with One Unit
  • In-Line Tube In Shell Evaporator
  • Titanium Helical Coil
  • Fresh or Saltwater Use
  • Compact Design
  • Quiet Operation
  • Black ABS Cover
  • Dual Stage Digital Temperature Controller
  • Ozone Friendly Refrigerant (134A)
Titan Air-Cooled Heat Pump
Sizing

A number of factors influence the correct size of heat pump required for your application. While standard Btu calculations can be applied, and our Heat Pump Specifications can offer some guidelines, the parameters of your application will be the deciding factor in correct size selection.

Titan Air-Cooled Heat Pump

Model No.

Nominal Tons

Nominal BTUH

Volts/phase

Amps RLA/LRA

Water flow (GPM)

Air Outlet (CFM)

H (In.)

L (in.)

W (In.)

HP-1

1.5

18000

208-240/1

6/38

20 – 40

1550

59

44

33

HP-2

2

24000

208-240/1

8.7/57

20 – 40

1550

63

44

33

HP-3

3

36000

208-240/1

14/91

20 – 40

2175

63

51

38

HP-33

3

36000

208-240/3

10.9/74

20 – 40

2175

63

51

38


HP-33-460

3

36000

460/3

5.5/38

20 – 40

2175

63

51

38


HP-4

4

48000

208-240/1

18.6/94

30 – 60

2500

67

51

38


HP-43

4

48000

208-240/3

13.7/101

30 – 60

2500

67

51

38


HP-43-460

4

48000

460/3

7/41

30 – 60

2500

67

51

38


HP-5

5

60000

208-240/1

25/148

30 – 60

3700

75

51

38


HP-53

5

60000

208-240/3

18.6/94

30 – 60

3700

75

51

38


HP-5-460

5

60000

460/3

9/71

30 – 60

3700

75

51

38


HP-6

7.5

90000

208-240/3

29/172

60 – 120

5200

65

51

42

HP-6-460

7.5

90000

460/3

15/94

60 – 120

5200

65

51

42

HP-7

10

120000

208-240/3

40/278

60 – 120

5200

74

61

46

HP-7-460

10

120000

460/3

15/90

60 – 120

5200

74

61

46

HP-15

15

180000

208-240/3

50/164

120 – 180

9750

78

111.5

53

HP-15-460

15

180000

460/3

25/100

120 – 180

9750

78

111.5

53


HP-20

20

240000

208-240/3

78/267

120 – 180

9750

91

111.5

53


HP-20-460

20

240000

460/3

40/142

120 – 180

9750

91

111.5

53


Specifications
  • 1 1/2 Hp – 20 Hp
  • Heat or Chill with one unit
  • Insulated Titanium Heat Exchanger
  • TRANE Condensing Unit
  • Dual Stage Digital Temperature Controller in NEMA4X enclosure
  • Built in Safety Flow Switch
  • Includes stainless steel stand
  • Fresh or Saltwater use
  • All units suitable for outdoor use

Titan Heat Pumps up to 5hp have a specialized spiral condenser coil which has proven to have superior heat transfer performance and capacity over conventional radially finned condenser coils, and has a much greater resistance to corrosion in harsh environments.

For Cooler Climates: If ambient air temperatures can fall below 55ºF when operating unit in cooling mode, then low ambient controls must be installed on the condensing unit. This will allow the unit to operate in cooling mode in air temperatures down to 0ºF.

When exposed to colder air temperatures ice may form on the condenser in which case the unit will automatically go into defrost mode based on a preset time interval.

In Heating Mode the heat pump will lose efficiency with air temps below 45ºF and it is recommended that you switch to electric or gas heat. Please consult Aqua Logic if you expect temperatures below 45oF. Precautions must be taken to ensure water flow is not interrupted to unit during freezing conditions to prevent exposed outdoor water lines and heat exchanger from freezing. If unit will not be in use during freezing conditions the outdoor plumbing and heat exchanger should be completely drained of water.

Titan Water-Cooled Heat Pump
Sizing

A number of factors influence the correct size of heat pump required for your application. While standard Btu calculations can be applied, and our Heat Pump Specifications can offer some guidelines, the parameters of your application will be the deciding factor in correct size selection.

Contact us today for help with sizing the perfect unit for your needs.

Specifications

Powder coating available for stainless steel stand at an added charge.

Coastal coating protection available for condensing units that may be exposed to salt air or corrosive environment. Additional charge will be incurred.

Stainless steel stand can be upgraded to 316SS at an additional charge.

Product Literature

CONNECT WITH OUR EXPERT TEAM

CUSTOMER SERVICE